Instrumentation Job Interview Questions

Answer  
# 1 Control valve can not be without positioner. The purpose of the positioner is to control the control valve stroke so as to keep the valve in desired position. The positioner receives signal from the controller, and send the boosted signal to the actuator to reach the desired position as and when the valve reaches the desired position the positioner cuts the boosted signal to the actuator and keeps the position.
Answer Submitted by: Admin
Is This Answer Correct?    35 Yes 10 No
Answer  
# 2 yes, we can use control valve without a positioner, in fact when the positioner is malfunctioning there is a provision to bypass it until possible to repair / replace, however we cannot get efficient control valve operation without positioner, so ideally positioner should be installed for control valves.
Answer Submitted by: Mahesh Tulsiani
Is This Answer Correct?    11 Yes 4 No
Answer  
# 3 Yes,we can use a control valve without a positioner.But when there is a deviation of the valve plug from the desired position decided by the controller due to some external disturbances,it cannot be rectified without a positioner.So its better to use a valve with a positioner.
Answer Submitted by: Vivek Narayanan
Is This Answer Correct?    4 Yes 2 No
Answer  
# 4 As per control application and process design/requirment still many pneumatic control loops available without positoner control valve. so my answer is yes.
Answer Submitted by: Amjad Ali
Is This Answer Correct?    0 Yes 1 No
Answer  
# 5 Yes but we are not control same like on off valve.
Answer Submitted by: Deenathayalan
Is This Answer Correct?    0 Yes 0 No
Answer  
# 6 If control valve bench set is 0.2 kg/cm2 to 1 kg/cm2 then we can use a control valve without positioner.
Answer Submitted by: Naveed Ahmad
Is This Answer Correct?    0 Yes 0 No
Submit New Question Place Your Answer

Previous Interview QuestionNext Interview Question
Why 4-20 mA signal is preferred over a 0-10V signal?What is Instrumentation Measurement?

Top: Can we use a control valve without positioner?
Instrumentation  Job Interview Question


Top Frequently Asked Instrumentation  Question
Frequently Asked Instrumentation  Job Interview Question


Top Frequently opened Other Professions Job Interview categories
Most popular Other Professions Job Interview categories

Comments About Can we use a control valve without positioner?

Share your valuable opinions, ideas and suggestions about Can we use a control valve without positioner?
While placing your comment your email address is required but won't be published any where else; Personal information will be kept confidential; we do not sell or release our respective visitors private information.
  1. Webmaster 23rd of May 2012

    Webmaster Said

    Tell us what you feel about Can we use a control valve without positioner?
    All comments will be published after review. No login or registration is required to post a comment on Can we use a control valve without positioner? We offer and invite you to submit your valuable comment now; Please be respectful of others when commenting. Insulting others, self-promotional comments, website promotional comments, marketing stuff, SEO Techniques, SMS-style content and off-topic comments will not be approved at this information portal.
    So start sharing your thoughts regarding Can we use a control valve without positioner?
    Thank you.

    • chhabiraj (1 Comment) 21st of August 2011

      chhabiraj Said

      Yes we can use valve without positioner.it will open or close depending on action as per giver air pressure.

Leave a Comment

Leave a Comment
  1.  Enter This Verification Code  Regenerate Verification Code  



Your reply will be added to the comment above (Below any other replies to this comment) -

Top Comments About: Can we use a control valve without positioner?
Comments on Can we use a control valve without positioner?

 
Top of Link batk to Can we use a control valve without positioner?
Link batk to Can we use a control valve without positioner?