Is it advisable to cool a fin fan by spraying demineralized water on it?

Submitted by: Administrator
Fin fan has carbon steel tubes with aluminum fins RESPONSE In a similar service, the fin fan suffered external corrosion when spraying it with demin water. The salt and oxygen in the air corrodes the air-cooler.

The gas is piped normally from an outside cylinder storage facility to a process control panel at approximately 60 psig. The panel-output chlorine pressure is 15 psig and a flow rate of approximately 0.03 scfm. Occasionally the flow control devices in the process panel are contaminated by what appears to be liquid chlorine. It seems that temperature variations in the iron transport pipe may have some influence on the liquid formation.

The condensation temperature of gaseous chlorine at 65 psig is 54 deg F. Thus, if your transport line is long, it is quite likely that ambient temperatures lower than 54 deg F could result in cooling the line enough to cause condensation of the chlorine gas. If you lower the transport pressure to 25 psig, the condensation temperature would be 24 deg F ..., which should significantly lower the likelihood of cold ambient temperature causing the gas to condense.
Submitted by: Administrator