Interviews Technical Support Engineer Interviews:Auto Body WorkerCamera TechnicianCar RepairmanCCTV Camera/ Device InstallerCCTV OperatorData Entry Operator (DEO)Die DeveloperElectric MechanicElectric Motor RepairerElectronic Media PerformersElevator TechnicianFilling Machine OperatorGenerator OperatorInstrumentationInstrumentation SpecialistLab ChemistLead GeneratorMusical Instrument MakerProduction OfficerRepairmanSharePoint DeveloperShoe MakerSolar Panel TechnicianTechnical EditorTechnical Support EngineerTechnician
Copyright © 2018. All Rights Reserved
Instrumentation Interview Question:
Can we use a control valve without positioner?
Submitted by: AdministratorControl valve can not be without positioner. The purpose of the positioner is to control the control valve stroke so as to keep the valve in desired position. The positioner receives signal from the controller, and send the boosted signal to the actuator to reach the desired position as and when the valve reaches the desired position the positioner cuts the boosted signal to the actuator and keeps the position.
Submitted by: Administrator
Submitted by: Administrator
yes, we can use control valve without a positioner, in fact when the positioner is malfunctioning there is a provision to bypass it until possible to repair / replace, however we cannot get efficient control valve operation without positioner, so ideally positioner should be installed for control valves.
Submitted by: Mahesh Tulsiani
Submitted by: Mahesh Tulsiani
Yes,we can use a control valve without a positioner.But when there is a deviation of the valve plug from the desired position decided by the controller due to some external disturbances,it cannot be rectified without a positioner.So its better to use a valve with a positioner.
Submitted by: Vivek Narayanan
Submitted by: Vivek Narayanan
As per control application and process design/requirment still many pneumatic control loops available without positoner control valve. so my answer is yes.
Submitted by: Amjad Ali
Submitted by: Amjad Ali
Yes but we are not control same like on off valve.
Submitted by: Deenathayalan
Submitted by: Deenathayalan
If control valve bench set is 0.2 kg/cm2 to 1 kg/cm2 then we can use a control valve without positioner.
Submitted by: Naveed Ahmad
Submitted by: Naveed Ahmad
Yes, we can.
By connecting the electrical controller output signal (4-20mA) to an I/P and connecting the I/P output signal (3-15psi) to the control valve diaphragm you can control the control valve.
You can also actuate the control valve by the output signal of a pneumatic controller directly.
The point is you are going to have an open loop control.
Submitted by: Adel Ahlenajafi
By connecting the electrical controller output signal (4-20mA) to an I/P and connecting the I/P output signal (3-15psi) to the control valve diaphragm you can control the control valve.
You can also actuate the control valve by the output signal of a pneumatic controller directly.
The point is you are going to have an open loop control.
Submitted by: Adel Ahlenajafi
Yes We Use Controle Without Positioner. In that case We use I/p Converter and Then we use pnuematic signal 3 to 15 Psi at in put and for signal regulation we use pnumetic controler. And we achieve our desire position.
Submitted by: Muhammad Farooq Abdullah
Submitted by: Muhammad Farooq Abdullah