Interviews Best Engineering Interviews:Aeronautical EngineeringAgricultural EngineeringApplied EngineeringAssociate EngineeringAutomobile EngineeringBio EngineeringBiomedical EngineerBiomedical EngineeringBuilding Services EngineeringCAD/CAE EngineerChemical EngineeringCivil EngineeringDAE Knitting EngineersDeputy Chief Financial OfficerDesktop EngineerDiesel MechanicElectrical EngineeringElectronics CommunicationsElectronics EngineeringEmbedded Software EngineerEnergy EngineeringEnergy Oil GasEngineeringGalvanizing EngineerIndustrial EngineeringInstrumentation EngineeringLaptop RepairerMachine Learning EngineerMachine OperatorMarine EngineeringMechanical EngineeringMechatronics EngineeringNetwork EngineerNuclear EngineeringPetroleum EngineeringPlant Reliability EngineerPlumberPre EngineeringProduction EngineerRF EngineerSystem EngineeringTextile Engineer
Copyright © 2018. All Rights Reserved
Instrumentation Engineering Interview Question:
What happen if i install my pressure transmitter below the elevation of pipe in natural gas service?
Submitted by: AdministratorAd
Pressure will be added up a bit more, see its detail:
1. Suppose,you want to install a pressure transmitter 10
meter below of pipe line.
2. Density of methane (Examlpe) 0.656 kg/m3 at 25C.
3. your pressure transmitter will show (10 x 1000 x0.656 =
6560mm) 6569 mm of water pressure more.
4. Suppose gas pressure is 20Kg/cm2, then due to this
elevation, transmitter will show 20.66Kg/cm2
Submitted by: Administrator
1. Suppose,you want to install a pressure transmitter 10
meter below of pipe line.
2. Density of methane (Examlpe) 0.656 kg/m3 at 25C.
3. your pressure transmitter will show (10 x 1000 x0.656 =
6560mm) 6569 mm of water pressure more.
4. Suppose gas pressure is 20Kg/cm2, then due to this
elevation, transmitter will show 20.66Kg/cm2
Submitted by: Administrator
Pressure transmitter in a gas service shall be installed above pipe line. If it is installed below pipeline, the moisture in the gas service gets trapped in the impulse line and acts like a cushion in your chairs which will provide you erroneous readings lesser than the actual pressure in the pipe line. if pressure transmitter is installed below pipeline, moisture to be collected in a separate condensate point and needs to be drained at a frequent interval .