How to use level tranasmitter in closed tank application?

Submitted by: Administrator
In closed systems, the transmitter location is
restricted by the maximum allowable distance
above the lower tap. In pressurized systems, this is
the same as the 1 atmosphere equivalent seen
previously. In sub-atmospheric systems (vacuum
systems), the transmitter should be mounted at or
below the lower tap. This ensures the transmitter
always sees a positive pressure on both the
measurement and the reference sides.
In two seal systems, the distance between the taps
becomes the reference offset from zero. The
calculations are the same regardless of where the
transmitter is mounted.